01423 340 000

Limited A1140-DC is available at low cost from stock - click here to purchase for next day delivery

Schneider PowerLogic PM5111 3 Phase Power MID meter 15th THD (METSEPM5111)

  • Accuracy rating- Class 0.5S
  • Alarms: 33 configurable
  • Back-lit LCD Screen
  • Current': 1A or 5A
  • Communications: Modbus RS485 serial port
  • Real time clock 
  • Multi-Tariff (4)
  • MID Certified 
  • Pulse: 1D/O (Not accessible via the display)
  • Parameters: I, V, W, Fq, PF, kWh, THD, TDD, VLN, VLL (Harmonics up to 15th for analysis)
  • Real-time clock
Enquire Now

Product Details

The Schneider PM5111 provides an excellent MID approved metering solution for highly accurate tenant and sub-billing applications.

In a single 96 x 96 mm unit, with a graphical display, all three phases, neutral and ground can be monitored simultaneously.

The meters have direct connection up to 690V L-L without voltage transformers complaint with CAT III; allowing more free panel space for the user.  


Product Specification

  • Device(EM5111): Power monitoring
  • Type of measurements: Active and reactive power (KVAR), Frequency (Hz), Power factor (0-1), Energy (W-KW), Voltage (V), Current (A)
  • Supply voltage: 125-250 V DC or 110-415 V AC (45-65 Hz)
  • Network frequency: 50 Hz - 60 Hz
  • [In] rated current: 1 A, 5 A
  • Type of network: 1P + Neutral, 3P (3Phase), 3P + Neutral
  • Power consumption in VA:10 VA at 415 V
  • Display type: Backlit LCD
  • Display resolution:128 x 128 pixels
  • Sampling rate:64 samples/cycle
  • Measurement current:10 mA- 9 A
  • Analogue input type: Voltage (impedance 5 MOhm)
  • Current (impedance 0.3 mOhm)
  • Communication port protocol: Modbus TCP/IP : 10/100 Mbit/s, insulation: 2500 V
  • Measurement voltage: 20/400 V AC 45-65 Hz between phase and neutral 35/690 V AC 45-65 Hz between phases
  • Frequency measurement range: 45-65 Hz
  • Number of outputs: 1 digital
  • Measurement accuracy: +/- 0.5 % voltage, +/- 0.5 % current, +/- 0.005 % power factor, +/- 0.05 % frequency, +/- 0.5 % apparent power, +/- 0.5 % active power, +/- 2 % reactive energy, +/- 0.5 % active energy
  • Accuracy class: Class 0.5S (active energy according to IEC 62053-22)
  • Insulation: 2500 V
  • Data recording: Data logs, Event logs, Min/max of instantaneous values, Time, stamping, Alarm logs, Maintenance logs
  • Memory capacity: 256 kB
  • Mounting mode: Flush-mounted
  • Mounting support: Framework
  • Standards: IEC 60529, IEC 61557-12, IEC 62053-22, EN 50470-1, EN 50470-3, IEC 62053-24
  • Width: 96 mm
  • Depth: 72 mm
  • Height: 96 mm
  • Product weight: 430g

Can't find what you're looking for?

or

Get in touch